- Capacity from 160 to 500 liters;
- Magnesium anode for additional anti-corrosion protection;
- Side inspection flange;
- Quality thermal protection of rigid polyurethane foam with thickness of 50 mm;
- Hole for mounting of thermoelectric heating element;
- Equipped with thermometer.
Buffer tank VTE-2
TECHNICAL DESCRIPTION
The calorifier is designed for heating water in bivalent systems, as well as for its accumulation and storage for DHW. The lower heat exchanger is intended for connection to low-temperature heat sources (e.g., solar collectors, heat pumps). The upper heat exchanger is optimized for integration with high-temperature sources, primarily used for supplementary heating The tank features a flanged inspection port with a sealed cover for periodic maintenance access. A fitting above the heat exchanger is provided to install an electric heating element. Two magnesium anodes ensure corrosion protection.
MATERIALS
Tank and heat exchanger are constructed from cold-rolled carbon steel with an internal double-layer enamel coating, baked at 860°C by DIN 4753 standards.
THERMAL INSULATION
Rigid polyurethane foam insulation, 50 mm thick, encased in a zippered “sky” finish casing, compliant with all requirements of the ErP 2009/125/EC Directive.
Overall connection dimensions
| Vof tank, l | Dimensions, mm | ST1, m2 | VT1, l | ST2, m2 | VT2, l | Mounting dimensions, mm | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| H | ØD | Ød | h1 | h2 | h3 | h4 | h5 | h6 | h7 | hf | hT1 | hT2 | hT3 | hT4 | |||||
| 200 | 1200 | 600 | 500 | 0,75 | 4,6 | 0,54 | 3,3 | 628 | 993 | 199 | 478 | 746 | 815 | 993 | 314 | 284 | 585 | 671 | 886 |
| 1½” | ½” | 1″ | ½” | ¾” | ½” | 1″ | 1″ | ||||||||||||
| 300 | 1760 | 600 | 500 | 1,27 | 7,66 | 0,85 | 5,1 | 862 | 1512 | 242 | 512 | 1088 | 1122 | 1512 | 287 | 242 | 782 | 942 | 1302 |
| 1½” | ½” | 1″ | ½” | ¾” | ½” | 1″ | 1″ | ||||||||||||
| 400 | 1407 | 750 | 650 | 1,65 | 10 | 0,76 | 4,6 | 813 | 1156 | 220 | 617 | 943 | 998 | 1156 | 331 | 302 | 775 | 858 | 1073 |
| 1½” | ½” | 1″ | ½” | ¾” | ½” | 1″ | 1″ | ||||||||||||
| 500 | 1674 | 750 | 650 | 2,25 | 13,7 | 1,06 | 6,4 | 986 | 1448 | 214 | 750 | 1165 | 1265 | 1448 | 324 | 299 | 944 | 1029 | 1330 |
| 1½” | ½” | 1″ | ½” | ¾” | ½” | 1″ | 1″ | ||||||||||||
| Model | Capacity | Weight | Isolation (rigid polyurethane foam) | Surface of heat exchanger | Tank of heat exchanger | Variable power in continuous operation mode (maximum heat exchanger output) *60-80/70-90°C |
Speed of continuous flow ΔT 35°C *60-80/70-90°C |
Max. amount of mixed water MIX 45°C (**15-60°C), Heat exchanger input power off |
Heat losses ΔT 45K |
|||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| S1 | S2 | S1 | S2 | S1 | S2 | S1 | S2 | S1 | S2 | |||||
| VTE-200-2 | 200 l | 70 kg | 50 mm | 0.75 m2 | 0.54 m2 | 4.6 l | 3.3 l | 23/30 kW | 13/20 kW | 558/648 l/h | 318/468 l/h | 225 l | 111 l | 2.5 kWh/24 h |
| VTE-300-2 | 300 l | 121 kg | 50 mm | 1.27 m2 | 0.85 m2 | 7.66 l | 5.1 l | 34/ – kW | 26/ – kW | 792/1092 l/h | 594/785 l/h | – l | – l | 2.1 kWh/24 h |
| VTE-400-2 | 400 l | 146 kg | 50 mm | 1.65 m2 | 0.76 m2 | 10 l | 4.6 l | 47/61 kW | 21/30 kW | 1002/1500 l/h | 470/648 l/h | 405 l | 200 l | 2.8 kWh/24 h |
| VTE-500-2 | 500 l | 158 kg | 50 mm | 2.25 m2 | 1.06 m2 | 13.7 l | 6.4 l | 61/73 kW | 35/47 kW | 1500/1795 l/h | 785/1002 l/h | 510 l | 250 l | 2.9 kWh/24 h |