• Gas
  • Electric boiler
  • Solid fuel boiler
  • Sun
  • Heat pumps
  • Hot water supply (HWS)
  • Capacity from 80 to 3000 liters;
  • Side inspection flange;
  • Quality thermal insulation class C (ErP) with thickness of 90 mm;
  • Hole for mounting of electric heating element;
  • Possible performance with tank working pressure 8 and 10 bar;
  • Hole for recirculation line.

Specifications

Capacity80-3000 l
Working pressure at heat exchanger input6 bar
Operating temperature of the tank95 °C
Warranty5 years

TECHNICAL DESCRIPTION

The DHW thermal storage tank is designed for the accumulation and storage of water preheated in an external heat exchanger for DHW. The tank’s design includes a flanged inspection hatch with a cover, intended for periodic service maintenance of the tank.

MATERIAL

The tank is made of AISI 316L (DIN 1.4404) stainless steel, meeting the highest hygienic requirements.

THERMAL INSULATION

PL/PVC100 mm polyester insulation in a zippered PVC casing
PU/PVC90 mm elastic polyurethane foam insulation in a PVC casing secured with straps
PL/ABS100 mm polyester insulation in an ABS plastic casing with plastic latches
PS/ABS100 mm high-efficiency rigid graphite polystyrene insulation in an ABS plastic casing.
Premium-class insulation complies with all requirements of the ErP 2009/125/EC Directive
Vof tank, l Dimensions, mm Mounting dimensions, mm
H ØD1 ØD Ød h1 h2 h3 h4 h9 h10 h11 h13 h14
400 1705 800 600 450 75 321 1161 1381 1001 296 856 1271 481
½” 1″ ¾”
500 1955 800 600 450 75 321 1411 1631 1131 296 956 1521 481
½” 1″ ¾”
750 2025 950 750 600 75 363 1453 1673 1173 338 998 1563 523
½” 1¼” 1″ ¾”
1000 2060 1050 850 700 75 380 1470 1690 1190 355 1015 1580 540
½” 1¼” 1″ ¾”
1500 2200 1200 1000 850 75 461 1551 1771 1271 436 1096 1661 621
½” 1½” 1¼” ¾”
2000 2300 1400 1200 1000 75 511 1601 1821 1321 486 1146 1711 671
½” 1½” 1¼” ¾”
3000 2410 1600 1400 1150 75 566 1656 1876 1376 541 1201 1766 726
½” 1½” 1¼” ¾”